Skip to content

EU · EudraLex Vol.4

EU GMP Annex 1 4.27

4. Premises › Cleanroom and clean air equipment qualification

Section text

For cleanroom classification, the total of particles equal to or greater than 0.5 and 5 µm should be measured. This measurement should be performed both at rest and in simulated operations in accordance with the limits specified in Table 1.

Table 1: Maximum permitted total particle concentration for classification

Maximum limits for total particle Maximum limits for total particle

≥ 0.5 µm/m[3] ≥ 5 µm/m[3] Grade

at rest in operation at rest in operation

Not specified (a) Not specified (a) A 3 520 3 520

Not specified (a) B 3 520 352 000 2 930

C 352 000 3 520 000 2 930 29 300

3 520 000 Not 29 300 Not D predetermined (b) predetermined (b)

(a) Classification including 5µm particles may be considered where indicated by the CCS or historical trends.

(b) For grade D, in operation limits are not predetermined. The manufacturer should establish in operation limits based on a risk assessment and routine data where applicable.

Source: European Commission, DG SANTE · © European Union. Reuse is authorised provided the source is acknowledged (Commission Decision 2011/833/EU on the reuse of Commission documents). · retrieved 2026-11-15

Weekly Newsletter

Get new findings like these every Monday

Every Monday we email the week's new findings and actions from the FDA, EMA, Health Canada and MFDS. Each one links to its record on our site, where you'll find the regulator's original document. We'll also let you know when the site gains new features. Unsubscribe any time with one click.

See recent findings first