The background environment for isolators or RABS should ensure the risk of transfer of contamination is minimized.

i. Isolators:

a. The background environment for open isolators should generally correspond to a minimum of grade C. The background for closed isolators should correspond to a minimum of grade D. The decision on the background classification should be based on risk assessment and justified in the CCS. b. Key considerations when performing the risk assessment for the CCS of an isolator should include (but are not limited to); the bio-decontamination programme, the extent of automation, the impact of glove manipulations that may potentially compromise ‘first air’ protection of critical process points, the impact of potential loss of barrier/glove integrity, transfer mechanisms used and activities such as set-up or maintenance that may require the doors to be opened prior to the final bio-decontamination of the isolator. Where additional process risks are identified, a higher grade of background should be considered unless appropriately justified in the CCS. c. Airflow pattern studies should be performed at the interfaces of open isolators to demonstrate the absence of air ingress.

ii. RABS:

The background environment for RABS used for aseptic processing should correspond to a minimum of grade B and airflow pattern studies should be performed to demonstrate the absence of air ingress during interventions, including door openings if applicable.

본문은 원문(영어)입니다. 국문 번역은 준비 중입니다.

출처: European Commission, DG SANTE · © European Union. Reuse is authorised provided the source is acknowledged (Commission Decision 2011/833/EU on the reuse of Commission documents). · 수집일 2026-11-15

Weekly Newsletter

이런 지적, 매주 월요일 한국어로 받아보세요

FDA·EMA·식약처의 새 지적과 조치를 공식 원문 링크와 함께 보내드립니다. 사이트에 새로운 기능이 생기면 함께 안내드립니다. 구독은 언제든 한 번의 클릭으로 해지할 수 있습니다.

이번 주 소식 먼저 보기

매주 월요일 발송 · 구독 신청 시 확인 메일이 발송됩니다 · 수신거부는 모든 메일 하단에서 가능합니다.