본문 바로가기

EU · EudraLex Vol.4

EU GMP Annex 1 4.25

4. Premises › Cleanroom and clean air equipment qualification

조항 원문

Cleanroom and clean air equipment qualification is the overall process of assessing the level of compliance of a classified cleanroom or clean air equipment with its intended use. As part of the qualification requirements of Annex 15, the qualification of cleanrooms and clean air equipment should include (where relevant to the design/operation of the installation):

i. Installed filter system leakage and integrity testing.

ii. Airflow tests - volume and velocity.

iii. Air pressure difference test.

iv. Airflow direction test and visualisation.

v. Microbial airborne and surface contamination.

vi. Temperature measurement test.

vii. Relative humidity test.

viii. Recovery test.

ix. Containment leak test.

Reference for the qualification of the cleanrooms and clean air equipment can be found in the ISO 14644 series of standards.

본문은 원문(영어)입니다. 국문 번역은 준비 중입니다.

출처: European Commission, DG SANTE · © European Union. Reuse is authorised provided the source is acknowledged (Commission Decision 2011/833/EU on the reuse of Commission documents). · 수집일 2026-11-15