EU · EudraLex Vol.4
EU GMP Annex 1 4.27
4. Premises › Cleanroom and clean air equipment qualification
조항 원문
For cleanroom classification, the total of particles equal to or greater than 0.5 and 5 µm should be measured. This measurement should be performed both at rest and in simulated operations in accordance with the limits specified in Table 1.
Table 1: Maximum permitted total particle concentration for classification
Maximum limits for total particle Maximum limits for total particle
≥ 0.5 µm/m[3] ≥ 5 µm/m[3] Grade
at rest in operation at rest in operation
Not specified (a) Not specified (a) A 3 520 3 520
Not specified (a) B 3 520 352 000 2 930
C 352 000 3 520 000 2 930 29 300
3 520 000 Not 29 300 Not D predetermined (b) predetermined (b)
(a) Classification including 5µm particles may be considered where indicated by the CCS or historical trends.
(b) For grade D, in operation limits are not predetermined. The manufacturer should establish in operation limits based on a risk assessment and routine data where applicable.